Microtek UPS SUPERMAX - SERIES - I

24x7
Select The Following Brands...


ONLINE UPS SUPERMAX - SERIES - I
Online UPS
MODEL'S NAME : SUPERMAX - SERIES - I 5KVA to 30KVA

Applications : Networking Equipment, Computer Rooms, Mission Critical Process, Bank, Office, Railways, Hospitals, Defence and Telecom Centers, all types of Single Ph. Loads.

Features :

  • True Online Double Conversion Technology.

  • Automatic Battery Charging in UPS Off Mode.

  • Advanced Battery Management, Wide Input Voltage Range.

  • Parallel Redundant / Hot Standby. (optional), Galvanic Isolation.

  • 1 Phase in ~ 1 Phase out (upto 10KVA), 3 Phase in ~ 1 Phase out (upto 30KVA).

  • Specially Designed to Suit Indian Power and Environment Conditions, Generator Compatible.

  • High End Micro Controller.

  • Short Circuit and Overload Protection.

Specifications :

Technical Specifications

Model

Supermax-Series - I

Capacity

 

5KVA to 30KVA

Technology

 

Double Conversion high Freq. Switching PWM, using IGBT's

Input

Voltage Range

 

160V AC~270V AC ±5V AC, Single Phase for upto 10KVA and 360V AC~450V AC ±5V AC, Three Phase for upto 30KVA

Frequency

 

45~55Hz

Phase

 

Single phase upto 10KVA and Three Phase from 5 to 30KVA

Generator Compatibility

 

Present

Output

Voltage

 

230V Ac ±1%

Frequency Range

 

50Hz ± 0.5%

THD (Liner Load)

 

<3%

THD (Non-Liner Load)

 

<5%

Overload Capability

 

125% for 2minuted / 150% for 30Seconds

Crest Factor

 

3:1 (max)

Shot Circuit Protection

 

Instant

Waveform

 

Pure Sine Wave

Manual Bypass   Inbuilt upto 15KVA

Static Bypass (optional)

 

<5ms

Inverter Efficiency

 

≥ 90% on rated full load

Overall Efficiency

 

≥ 80%

Battery

DC Voltage

 

180 / 360 VDC

Mimic Control Panel

 

LED for UPS status and LCD for Voltage, Current & Frequency

Audible Alarm

 

For Battery Low / DC High / Output High / Overload

Noise Level

 

≤ 50dB

Transient Response

 

For 100% step load charge, ± 5% and recovers to normal within 20 miliseconds.

Ambient Temperature / Relative Humidity

 

0-45° C / 0-95% Non-Condensing

Cooling

 

Forced Aircooled


HR